Prof. Dr. Thorsten Jungmann (last updated 2025-12-07)
Relates to EE1-04 Resistance
Task
When a photovoltaic system is installed, an earthing cable made of copper is laid (). The electric line has a length of and a cross-section of .
a) Calculate the conductor resistance of the earthing cable at .
b) What is the conductance of the earthing cable?
c) In the event of an earth fault, a current of flows briefly. What voltage drop occurs across the earthing cable?
Solution
a)
b)
c)
Solution
Given
Given explicitly:
- Cable length:
- Conductor cross-section:
- Material: copper
- Earth fault current:
Known:
- Resistivity of copper (20 °C):
- Conductor resistance:
- Conductance:
- Ohm’s law:
where:
- the resistance in ohms ()
- the resistivity in
- the length in metres ()
- the cross-sectional area in square millimetres ()
- the conductance in siemens ()
- the current in amperes ()
- the voltage drop in volts ()
Required
a) Conductor resistance in
b) Conductance in
c) Voltage drop in the event of an earth fault in
a) Conductor resistance
The conductor resistance results from the resistivity, the length and the cross-section:
Note
For earthing cables, it is important that the resistance is as low as possible so that high currents can flow in the event of a fault and the protective devices (e.g. fuses, residual-current circuit breakers) trip reliably.
b) Conductance
The conductance is the reciprocal of the resistance:
Check: ✔
c) Voltage drop in the event of an earth fault
The voltage drop across the earthing cable at an earth fault current of :
Practical significance
A voltage drop of about is acceptable in the event of an earth fault. The touch voltage at the earth electrode would be correspondingly low. In practice, resistances in the range below a few ohms are often aimed for in earthing systems (cf. DIN VDE 0100-540).