Prof. Dr. Thorsten Jungmann (last updated 2025-12-07)

Relates to EE1-04 Resistance


Task

When a photovoltaic system is installed, an earthing cable made of copper is laid (). The electric line has a length of and a cross-section of .

a) Calculate the conductor resistance of the earthing cable at .

b) What is the conductance of the earthing cable?

c) In the event of an earth fault, a current of flows briefly. What voltage drop occurs across the earthing cable?


Solution

Given

Given explicitly:

  • Cable length:
  • Conductor cross-section:
  • Material: copper
  • Earth fault current:

Known:

  • Resistivity of copper (20 °C):
  • Conductor resistance:
  • Conductance:
  • Ohm’s law:

where:

Required

a) Conductor resistance in
b) Conductance in
c) Voltage drop in the event of an earth fault in


a) Conductor resistance

The conductor resistance results from the resistivity, the length and the cross-section:

Note

For earthing cables, it is important that the resistance is as low as possible so that high currents can flow in the event of a fault and the protective devices (e.g. fuses, residual-current circuit breakers) trip reliably.

b) Conductance

The conductance is the reciprocal of the resistance:

Check: ✔

c) Voltage drop in the event of an earth fault

The voltage drop across the earthing cable at an earth fault current of :

Practical significance

A voltage drop of about is acceptable in the event of an earth fault. The touch voltage at the earth electrode would be correspondingly low. In practice, resistances in the range below a few ohms are often aimed for in earthing systems (cf. DIN VDE 0100-540).